| ■ Built-in Type Ni-MH Battery Pack for Nonstop Power Supply |
![]() External view of BS06B-H24/2.5L ![]() External view of BS06A-H24/2.5L (top cover is removed.) |
|
||||||||||||||||||||||||||
Major Specifications
|
Item |
Specifications |
Conditions |
|
Nominal battery voltage |
16.8 V | Closed type Nickel-Metal Hydrate battery |
|
Rated battery capacity |
2.5 Ah | |
|
Maximum output capacity |
310 W*1 | At ambient temperature ≥ 20°C |
| Ratings of fuse | 30 A, 32 V | |
|
Operating temperature/humidity |
0°C to 50°C / 10% to 90%RH*2 |
With heater (for
temperature control) connected to the peripheral connector
of power supply. |
|
Storage temperature/humidity |
≤ 1 year: -20°C ≤
T < 35°C/10%
to 95%RH |
At no condensation. |
|
Weight |
1.8 kg typ. |
|
| Dimensions | 146W x 38D x 181H mm | |
|
Component with limited life |
Battery pack |
Periodic maintenance and replacement are required. |
| Storage conditions | For a long-term storage over 6 months, recharge battery at least once a year. Recommended charge cycle is every 6 months. (If not recharged within the aforementioned term, its charge capacity may not be thoroughly recovered by recharging.) | |
|
Warranty |
1 year after delivery to customer. For a defect under responsibility of Nipron, battery pack is repaired or replaced with new one at no charge. Warranty does not apply to the failures caused by over-discharge or the uses that do not meet specified conditions. |
|
Note 1: When the efficiency
of nonstop power supply in DC input operating mode (no AC input) is, for
example, 68%, the maximum output power capacity of the nonstop power supply
is 210.8 W (equal to 310 W x 0.68).
Note 2: When the heater is not used,
the battery output current must be derated (suppressed) at ambient temperature
below 15°C.
BS06A/B Series
Battery Pack Configuration Guide
|
Model number |
Recommended use |
Note |
|
BS06A-H24/2.5L |
For battery backup of power supply against usual power outage. | Suitable for less than tens of backup operation a year. |
|
BS06B-H24/2.5L |
For frequent charge/discharge operation such as battery backup performed each time the PC shuts down*1. Also suitable for the backup against usual power outage. | With a coercive convection cooling function (cooling fan controlled by a thermo-sensing circuitry) |
|
|
|
|
|
|
|